| Brand Name: | Deye |
| Model Number: | SUN-90K-G03 |
| MOQ: | 1 piece |
| Price: | $1,300-1,400 / piece |
Model | SUN-90K-G03 | SUN-75K-G03 | SUN-80K-G03 | SUN-90K-G03 | SUN-100K-G03 | SUN-110K-G03 | ||||||
Input Side | ||||||||||||
Max. DC Input Power (kW) | 135 | 97.5 | 104 | 135 | 150 | 150 | ||||||
Max. DC Input Voltage (V) | 1000 | |||||||||||
Start-up DC Input Voltage (V) | 250 | |||||||||||
MPPT Operating Range (V) | 200-850 | |||||||||||
Max. DC Input Current (A) | 40+40+40+40+40+40 | 40+40+40+40+40+40 | ||||||||||
Max. Short Circuit Current (A) | 60+60+60+60+60+60 | 60+60+60+60+60+60 | ||||||||||
No.of MPP Trackers | 6 | 6 | ||||||||||
No.of Strings per MPP Tracker | 4+4+4+4+4+4 | 4+4+4+4+4+4 | ||||||||||
Output Side | ||||||||||||
Rated Output Power (kW) | 90 | 75 | 80 | 90 | 100 | 110 | ||||||
Max. Active Power (kW) | 90 | 75 | 80 | 90 | 100 | 110 | ||||||
Rated Output Voltage/Range (V) | 3L/N/PE 220/380V, 230/400V 0.85Un-1.1Un (this may vary with grid standards) | |||||||||||
Rated Grid Frequency (Hz) | 50 / 60 (Optional) | |||||||||||
Operating Phase | Three Phase | |||||||||||
Rated AC Grid Output Current (A) | 136.4/130.5 | 113.7/108.7 | 121.3/116 | 136.4/130.5 | 151.6/145 | 166.7/159.5 | ||||||
Max. AC Output Current (A) | 136.4/130.5 | 113.7/108.7 | 121.3/116 | 136.4/130.5 | 151.6/145 | 166.7/159.5 | ||||||
Power Factor Adjustment Range | 0.8 leading to 0.8 lagging | |||||||||||
Total Harmonics Current Distortion (THDi) | <3% | |||||||||||
DC Injection Current (mA) | <0.5% | |||||||||||
Grid Frequency Range | 45-55 or 55-65 (Optional) | |||||||||||
Efficiency | ||
Max. Efficiency | 98.8% | |
Euro Efficiency | 98.3% | |
MPPT Efficiency | >99% | |
Protection | ||
DC Reverse-Polarity Protection | Yes | |
AC Short Circuit Protection | Yes | |
AC Output Overcurrent Protection | Yes | |
Output Overvoltage Protection | Yes | |
Insulation Resistance Protection | Yes | |
Ground Fault Monitoring | Yes | |
Anti-islanding Protection | Yes | |
Temperature Protection | Yes | |
Integrated DC Switch | Yes | |
Remote Software Upload | Yes | |
Remote Change of Operating Parameters | Yes | |
Surge Protection | DC Type II / AC Type II | |
General Data | ||
Cabinet Size (WxHxD mm) | 826×516×312.7 (Excluding Connectors and Brackets) | |
Weight (kg) | 81 | |
Topology | Transformerless | |
Internal Consumption | <1W (Night) | |
Running Temperature | -25 to +65℃, >45℃ Derating | |
Ingress Protection | IP65 | |
Noise Emission (Typical) | ≤55 dB | |
Cooling Concept | Smart Cooling | |
Permissible Altitude (m) | 4000 | |
Warranty | 5 Years | |
Grid Connection Standard | IEC 61727, IEC 62116, CEI 0-21, CEI 0-16, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G99, VDE-AR-N 4105, VDE-AR-N 4110 | |
Operating Surroundings Humidity | 0-100% | |
Safety / EMC Standard | IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 | |
Features | ||
Display | LCD 240 × 160 | |
Interface | RS485/RS232/Wifi/LAN | |