* 8 MPP trackers, Max. effiffifficiency up to 98.8%
* Zero export application, VSG application
* String intelligent monitoring (optional)
* Wide output voltage range
* Anti-PID function (Optional)
* Type II DC/AC SPD
| Brand Name: | Deye |
| Model Number: | SUN-120/125/130/135/136-G01P3-EU-AM8 |
| MOQ: | 1 piece |
| Price: | $3,050-3,150 / piece |
Model | SUN-120K-G01P3 | SUN-125K-G01P3 | SUN-130K-G01P3 | SUN-135K-G01P3 | SUN-136K-G01P3 | ||||
PV String Input Date | |||||||||
Max. PV Input Power(kW) | 180 | 187.5 | 195 | 202.5 | 204 | ||||
Max. PV Input Voltage(V) | 1100 | ||||||||
Start-up Voltage(V) | 250 | ||||||||
MPPT voltage range(V) | 200-1000 | ||||||||
Rated PV Input voltage(V) | 600 | ||||||||
Max. Input Short Circuit Current (A) | 60+60+60+60+60+60+60+60 | ||||||||
Max. Operating PV Input Current(A) | 40+40+40+40+40+40+40+40 | ||||||||
No. of MPP Trackers/No. of Strings per MPP Tracker | 8/4+4+4+4+4+4+4+4 | ||||||||
AC Output Side | |||||||||
Rated AC Output Active Power(kW) | 120 | 125 | 130 | 135 | 136 | ||||
Max. AC Output Apparent Power(kVA) | 132 | 135 | 135 | 135 | 136 | ||||
Rated AC output current (A) | 181.9/174 | 189.4/181.2 | 197/188.5 | 204.6/195.7 | 206.1/197.2 | ||||
Max. AC Output Current(A) | 200/191.4 | 204.6/195.7 | 204.6/195.7 | 204.6/195.7 | 206.1/197.2 | ||||
Rated output voltage/range (V) | 220/380V, 230/400V 0.85Un-1.1Un | ||||||||
Grid Connection Form | 3L+N+PE | ||||||||
Rated Output Grid Frequency/range(Hz) | 50/45-55, 60/55-65 | ||||||||
Power Factor Adjustment Range | 0.8 leading to 0.8lagging | ||||||||
Total Current Harmonic Distortion THDi | <3% | ||||||||
DC Injection Current | <0.5%ln | ||||||||
Efficiency | |||||||||
Max. Efficiency | 98.8% | ||||||||
Euro Efficiency | 98.2% | ||||||||
MPPT Efficiency | >99% | ||||||||
Equipment Protection | |||||||||
DC Polarity Reverse Connection Protection | YES | ||||||||
AC Output Overcurrent Protection | YES | ||||||||
AC Output Overvoltage Protection | YES | ||||||||
AC Output Short Circuit Protection | YES | ||||||||
Thermal Protection | YES | ||||||||
DC Terminal Insulation Impedance Monitoring | YES | ||||||||
DC Component Monitoring | YES | ||||||||
Ground Fault Current Monitoring | YES | ||||||||
Power Network Monitoring | YES | ||||||||
Arc Fault Circuit Interrupter (AFCI) | Optional | ||||||||
Island Protection Monitoring | YES | ||||||||
Earth Fault Detection | YES | ||||||||
Overvoltage Load Drop Protection | YES | ||||||||
Residual Current (RCD) Detection | YES | ||||||||
Surge Protection Level | TYPE II(DC),TYPE II(AC) | ||||||||
Interface | |||||||||
Communication Interface | RS485/RS232 | ||||||||
Monitor Mode | GPRS/WIFI/Bluetooth/4G/LAN(optional) | ||||||||
General Data | |||||||||
Operating Temperature Range (°C) | ‘-25 to +60℃, >45℃ Derating | ||||||||
Permissible Ambient Humidity | 0~100% | ||||||||
Permissible Altitude (m) | 4000m | ||||||||
Noise (dB) | ≤ 65 | ||||||||
Ingress Protection(IP) Rating | IP 65 | ||||||||
Inverter Topology | Non-Isolated | ||||||||
Over Voltage Category | OVC II(DC),OVC III(AC) | ||||||||
Cabinet Size (WxHxD mm) | 1006mm*516mm*325.5mm(Excluding connectors and brackets) | ||||||||
Weight [kg] | 103 | ||||||||
Warranty | 5 years | ||||||||
Type Of Cooling | Intelligent air cooling | ||||||||
Grid Regulation | IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G99, VDE-AR-N 4105 | ||||||||